OMRON Corporation (FA and control equipment)

69-5822-21 [Discontinued]H5CX-L8-N H5CX-L8-N

Spec

  • Power supply voltage: 100~240 VAC (50/60 Hz)
  • Allowable voltage variation range: 85~ 110% of rated power supply voltage
  • Power Consumption: Approx. 6.2VA
  • Time specification (number of ranges): 10
  • Setting Time Range (Range): 0.001~9.999 s, 0.01~99.99 s, 0.1~999.9 s, 1~9999 s, 0.1~999.9min, 1~9999min, 0.1~999.9h, 1~9999h, 1 s to 99min 59 s, 1min to 99h 59min
  • Input method: Voltage-free input
  • Non-contact input: Impedance at short circuit: 1 kΩ or less (outflow current at 0 Ω: approx. 12 mA), Residual voltage at short circuit: 3 V or less, Impedance at open circuit: 100 kΩ or more (Use a DC power supply of 30 V or less.)
  • Contact input: Use a contact that can open and close 10 V 5 mA sufficiently.
  • Applicable 2 wire type sensor: Leakage current: 1.5 mA or less, Switchable capacity: 5 mA or more, Residual voltage: 3.0 VDC or less, Working voltage: 10 VDC.
  • Output modes: A: signal on delay (I), A-1: signal on delay (II), A-2: power on delay (I), A-3: power on delay (II), b: flicker (I), b-1: flicker (II), d: signal off delay, E: interval, F: summation, Z: ON/OFF duty variable, S: stopwatch, toff: flicker off start (I), ton: flicker on start (I), toff-1: flicker off start (II), ton-1: flicker on start (II)
  • Control Output (Contact Output): 1c (Limited Time), Resistance Load: 250 VAC/30 VDC 5A (cosφ=1), Minimum Applicable Load: 5 VDC 10 mA (P level, reference value)
  • Resetting method: Power reset (depending on output mode)/Auto reset (depending on output mode)/External reset/Manual reset
  • Power reset: Minimum power-open time: 0.5 s (Excludes A-3, b1, F, ton-1, and toff-1 modes)
  • Display mode: addition (UP) display, subtraction (DOWN) display (switching)
  • Display method: 7-segment negative LCD 4-digit
  • Character height: Time value: 12 mm (red), Settings: 6 mm (green)
  • Key protect method: Key protect switch
  • Power Outage Memory: EEP-ROM (Number of Rewrites: 100,000 or More Memory Time: 10 or More Years)
  • Operating Temperature Range: -10~55°C(Do not freeze or dew condense.), When Attached Closely: -10~50°C(Do not freeze or dew condense.)
  • Storage Temperature Range: – 25~70°C(Do not freeze or dew condense.)
  • Operating Humidity Range: 25~85%
  • Variation in operating time: Power start: ±0.01%±0.05 s or less (percentage of set value), Signal start: ±0.005%±0.03 s or less (percentage of set value)
  • Setting error: Power start: ±0.01%±0.05 s or less (percentage of set value), Signal start: ±0.005%±0.03 s or less (percentage of set value)
  • Effect of voltage: Power start: ±0.01%±0.05 s or less (percentage of set value), Signal start: ±0.005%±0.03 s or less (percentage of set value)
  • Temperature effect: Power start: ±0.01%±0.05 s or less (percentage of set value), Signal start: ±0.005%±0.03 s or less (percentage of set value)
  • Insulation Resistance: Between Conductive Part Terminal and Exposed Uncharged Metal Part: 100 MΩ or More (at 500 VDC Mega), Between Discontinuous Contact: 100 MΩ or More (at 500 VDC Mega)
  • Withstand voltage: between charged metal part and non-charged metal part: 2000 VAC 50/60Hz 1min, between power supply and input circuit: 2000 VAC 50/60Hz 1min, between control output, power supply and input circuit: 2000 VAC 50/60Hz 1min, between discontinuous contacts: 1000 VAC 50/60Hz 1min
  • Impulse voltage: between power terminals: 5 kV, between conductive terminal and exposed uncharged metal part: 5 kV
  • Noise resistance: between power terminals: ±1.5 kV, between input terminals: ±600 kV, square wave noise by noise simulator, pulse width 100 ns/1 μs, rise 1 ns
  • Electrostatic Resistance: 8 kV (malfunction), 15 kV (destruction)
  • Vibration Resistance: Durability: 10~55 Hz Single Amplitude 0.75 mm 3 Direction 2h Each, Malfunction: 10~55 Hz Single Amplitude 0.35 mm 3 Direction 10min Each
  • Shock Resistance: Endurance: 300 m/s**2, 3 times each in 3 axes, Malfunction: 100 m/s**2, 3 times each in 6 directions
  • Life: Electrical: 100,000 times or more (250 VAC, 5 A resistance load, 1800 times/h, 23°C), Mechanical: 10 million times or more (Unloaded opening/closing frequency 1800 times/h, 23°C)
  • Protective structure: IEC standard IP66, UL508 Type4X (indoor) (when using waterproof packing type Y92S -29)
  • Mounting method: embedded mounting, surface mounting (shared)
  • External connection method: 8-pin socket
  • Case Color: Black (Munsell N1.5)
  • Applicable Socket: P2CF-08, P2CF-08-E, P3G-08
  • Optional Parts: Soft Cover: Y92A-48F1, Hard Cover: Y92A-48, Embedded Mounting Adapter: Y92F-30/Y92F-45/Y92F-38, Waterproof Packing: Y92S-29, Replacement Front Panel: Y92P-CXT4 S/Y92P-CXT4G/Y92P-CXT4B
  • Weight: Body: Approx. 115 g
  •  
Order No. 69-5822-21
Model No. H5CX-L8-N
JAN Code 4548583745186
Standard price JPY: 16,200 USD: 101.55
Excange rate 1USD= 159.53JPY
Valid price in Japan
Quantity 1piece
  Discontinued